SunGoldPower SGH48100T Heated 5.12kWh Rack Battery - 1 Battery SunGoldPower SGH48100T Heated 5.12kWh Rack Battery
SKU: SGH48100T
- Nominal storage 5.12–20.48kWh options
- Battery system 51.2V / LiFePO4
- Installation Heated rack module
SGH48100T: choose storage that fits your system
Choose one, two or four SGH48100T modules for 5.12kWh, 10.24kWh or 20.48kWh of nominal storage. Each 51.2V 100Ah LiFePO4 module includes charger-powered heating for a correctly configured cold-weather battery bank.

Capacity, charging and load support
Each module uses up to 50A standard charge/discharge current, 70A maximum charging and 100A maximum discharge when the initial temperature is at most 30°C. The 120–200A rating lasts only 15 seconds. A larger pack increases energy; its approved continuous output still depends on cabling, current sharing, the inverter and temperature.
- 1 battery: 5.12kWh nominal / 100Ah
- 2 batteries: 10.24kWh nominal / 200Ah in parallel
- 4 batteries: 20.48kWh nominal / 400Ah in parallel
Installation and temperature limits
Each module measures 490 × 441 × 133mm (19.3 × 17.3 × 5.2in) and weighs approximately 47kg (103lb). Allow rack load capacity and service clearance for every module. The rack cabinet and inverter are separate; the selected battery count is not a complete solar system.
The heater starts between −25°C and 5°C when the charging-current condition is met (at least 0.08C, or 8A for a 100Ah module), and stops at 12°C. Below −10°C, incoming charging current goes to heating first. Normal charge operation is specified at −10–50°C with the heater sequence; discharge is −20–50°C. Heater current is additional to BMS-measured charge current.


Expansion and inverter communication
SunGoldPower documents up to 32 matching modules in parallel, totaling 163.84kWh nominal. The 1-, 2- and 4-battery selections keep the 51.2V nominal system voltage; they do not multiply voltage. Follow the manual for addressing, grounding, branch protection and inverter communications.
What’s included
Per battery module; package quantities update with your selected option.
- 1 × SGH48100T heated 5.12kWh battery
- 1 × User manual
- 6 × M6 floating nuts
- 4 × Combination screws
- 2 × M8 hex bolts
- 1 × Positive parallel cable — 250mm
- 1 × Negative parallel cable — 250mm
- 1 × Positive output cable — 1.5m
- 1 × Negative output cable — 1.5m
- 1 × Grounding cable — 300mm
- 1 × Battery communication cable — 250mm
The Package Includes tab shows the exact quantities for the selected option. One, two and four modules include matching multiples of the manual-listed accessories. Rack cabinets and inverters are separate.
Compare SunGoldPower battery options
SG48100M wall battery · SGH48100T heated rack battery · Powerwall X 10.24kWh · PowerMax 314 Outdoor · CoreX 5 Pro rack battery · CoreX 5 Elite wall battery.
Browse SunGoldPower batteries, 48V-class lithium storage and SunGoldPower inverters. Select the exact supported battery and inverter configuration before ordering.
Documents, warranty and model details
The current manual supplies the full technical table and illustrated packing list; a separate exact-model datasheet was not found on the manufacturer page. The attached Intertek UL 1973 certificate specifically names SGH48100T.
SGH48100T user manual (PDF) · SGH48100T UL 1973 certificate (PDF)
10-year manufacturer warranty; installation, use and exclusions subject to manufacturer terms. More than 7,000 cycles per manufacturer retail claim; actual life depends on conditions.
| Battery Chemistry | LiFePO4 (LFP) |
|---|---|
| Rated Voltage | 51.2 V nominal; 48V-class system |
| Warranty | 10-year manufacturer warranty; installation, use and exclusions subject to manufacturer terms |
| Inverter Compatibility | Confirm exact inverter model, firmware, communication protocol and cable pinout; matching nominal voltage alone is insufficient |
| Connection Method | Manufacturer-approved parallel arrangement; do not wire these storage modules in series |
| Model / SKU | SGH48100T; selected pack SKU varies |
| Product Type | Heated rack storage battery |
| Available Variants | 1 battery: 5.12 kWh; 2 batteries: 10.24 kWh; 4 batteries: 20.48 kWh nominal |
| Nominal Capacity | 100 Ah per module |
| Nominal Energy | 5.12 kWh per module at 0.5C |
| Usable Energy | 4.92 kWh per module at 0.5C; AC-delivered energy depends on inverter and reserve |
| Voltage Range | 44.8–57.6 V |
| Charge Voltage | 56.0 V |
| Float Charge Voltage | 54.6 V |
| Standard Charge / Discharge Current | At most 50 A per module |
| Maximum Charge Current | 70 A per module |
| Maximum Discharge Current | 100 A per module; initial temperature at most 30°C |
| Peak Discharge Current | 101–119 A for 5 min; 120–200 A for 15 sec; not continuous output |
| Parallel Expansion | Up to 32 matching modules, 163.84 kWh nominal |
| Heater Activation | −25 to 5°C with charge current at least 0.08C; heater current additional to BMS current |
| Heater Stop Temperature | 12°C; manual includes first-full-charge delay condition |
| Charge Temperature Range | −10–50°C with specified heater sequence; below −10°C incoming charge heats first |
| Discharge Temperature Range | −20–50°C |
| Storage Temperature | 0<T<30°C for less than 6 months; −10<T<45°C for less than 3 months |
| Recommended Environment | 15–35°C, 5–75% RH |
| Dimensions | 490 × 441 × 133 mm (19.3 × 17.3 × 5.2 in), each module |
| Weight | Approximately 47 kg (103 lb), each module |
| Communication | RS485 / CAN |
| Cycle Life | More than 7,000 cycles per manufacturer retail claim; actual life depends on conditions |
| Design Life | 15-year manufacturer claim; not warranty duration |
| Certification Evidence | Intertek UL 1973 certificate 100013197AHM-001; model SGH48100T |
| Included Components (Per Module) | 1 × SGH48100T heated 5.12kWh battery; 1 × User manual; 6 × M6 floating nuts; 4 × Combination screws; 2 × M8 hex bolts; 1 × Positive parallel cable — 250mm; 1 × Negative parallel cable — 250mm; 1 × Positive output cable — 1.5m; 1 × Negative output cable — 1.5m; 1 × Grounding cable — 300mm; 1 × Battery communication cable — 250mm |
| Selected SKU | SGH48100T |
| Selected Battery Quantity | 1 |
| Selected Nominal Energy | 5.12 kWh |
| Selected Parallel Capacity | 100 Ah at 51.2 V nominal |
| Selected Package Contents | 1 × SGH48100T heated 5.12kWh battery; 1 × User manual; 6 × M6 floating nuts; 4 × Combination screws; 2 × M8 hex bolts; 1 × Positive parallel cable — 250mm; 1 × Negative parallel cable — 250mm; 1 × Positive output cable — 1.5m; 1 × Negative output cable — 1.5m; 1 × Grounding cable — 300mm; 1 × Battery communication cable — 250mm |
| Selected variant SKU | SGH48100T |
Product reference specifications
Specifications for the selected option are shown above. These product reference details describe the listing and its available configurations.
| Battery Chemistry | LiFePO4 (LFP) |
|---|---|
| Rated Voltage | 51.2 V nominal; 48V-class system |
| Warranty | 10-year manufacturer warranty; installation, use and exclusions subject to manufacturer terms |
| Inverter Compatibility | Confirm exact inverter model, firmware, communication protocol and cable pinout; matching nominal voltage alone is insufficient |
| Connection Method | Manufacturer-approved parallel arrangement; do not wire these storage modules in series |
| Model / SKU | SGH48100T; selected pack SKU varies |
| Product Type | Heated rack storage battery |
| Available Variants | 1 battery: 5.12 kWh; 2 batteries: 10.24 kWh; 4 batteries: 20.48 kWh nominal |
| Nominal Capacity | 100 Ah per module |
| Nominal Energy | 5.12 kWh per module at 0.5C |
| Usable Energy | 4.92 kWh per module at 0.5C; AC-delivered energy depends on inverter and reserve |
| Voltage Range | 44.8–57.6 V |
| Charge Voltage | 56.0 V |
| Float Charge Voltage | 54.6 V |
| Standard Charge / Discharge Current | At most 50 A per module |
| Maximum Charge Current | 70 A per module |
| Maximum Discharge Current | 100 A per module; initial temperature at most 30°C |
| Peak Discharge Current | 101–119 A for 5 min; 120–200 A for 15 sec; not continuous output |
| Parallel Expansion | Up to 32 matching modules, 163.84 kWh nominal |
| Heater Activation | −25 to 5°C with charge current at least 0.08C; heater current additional to BMS current |
| Heater Stop Temperature | 12°C; manual includes first-full-charge delay condition |
| Charge Temperature Range | −10–50°C with specified heater sequence; below −10°C incoming charge heats first |
| Discharge Temperature Range | −20–50°C |
| Storage Temperature | 0<T<30°C for less than 6 months; −10<T<45°C for less than 3 months |
| Recommended Environment | 15–35°C, 5–75% RH |
| Dimensions | 490 × 441 × 133 mm (19.3 × 17.3 × 5.2 in), each module |
| Weight | Approximately 47 kg (103 lb), each module |
| Communication | RS485 / CAN |
| Cycle Life | More than 7,000 cycles per manufacturer retail claim; actual life depends on conditions |
| Design Life | 15-year manufacturer claim; not warranty duration |
| Certification Evidence | Intertek UL 1973 certificate 100013197AHM-001; model SGH48100T |
| Included Components (Per Module) | 1 × SGH48100T heated 5.12kWh battery; 1 × User manual; 6 × M6 floating nuts; 4 × Combination screws; 2 × M8 hex bolts; 1 × Positive parallel cable — 250mm; 1 × Negative parallel cable — 250mm; 1 × Positive output cable — 1.5m; 1 × Negative output cable — 1.5m; 1 × Grounding cable — 300mm; 1 × Battery communication cable — 250mm |
Frequently Asked Questions